Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2016, 10:11 AM
  • H 0577_H 0576_05052016_031602.mp4

Date
05/05/2016
W/O
568671
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00188
PipeID
P11001
Time
3:11 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3340
Sewer Name
H JOINT OUTFALL H - UNIT 8E
City
BALDWIN PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
19
Purpose
Routine Assessment
Project
WO_568671_TV15173_MAY2016
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
H 0577
Downstream MH
H 0576
Dir. of Survey
Downstream
Length Surveyed
355.4 ft.
Total Length
355.4 ft.
Structural Index
3
Structural Quick
3M2M
Structural Rating
350
O&M Index
2
O&M Quick
2M00
O&M Rating
144
Overall Index
2
Overall Quick
Overall Rating
494
Pipe schematic from manhole H 0577 to H 0576
MH: H 0577MH: H 0576downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 05770 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK.0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 25 %of cross sectional area2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start49.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"58.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"82.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"106 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"114.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"154.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"202.6 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS235.9 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS244 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"283.8 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"292.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"316.3 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"340.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"348.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"353.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish353.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish353.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE353.8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish355.4 ft. AMH - Downstream Manhole, Survey Ends - H 0576

Observation photos (7)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    202.6 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    235.9 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • General Observation - COCKROACHES IN MANHOLE

    353.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (28)

DistanceCodeObservation
353.8SSS
202.6TFDROOTS
49.6TFC
340.9TFC
2TFC
348.9TFA
235.9TFDROOTS
355.4AMHH 0576
2SAV
0AMHH 0577
316.3TBA
0MWM
2SSS
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK.
154.8TFA
0MGOCOCKROACHES IN MANHOLE
353.8DAGS
353.8MGOCOCKROACHES IN MANHOLE
2DAGS
0MWL
353.8SAV
106TFA
292.6TFC
58.1TFC
283.8TBA
114.4TFC
82.3TFC
244TBA

Properties (5)

additional_info
SC305617
custom_field_two
3
customer
LACSD
datetime
2016-05-05T03:11:04-07:00
sewer_category
GRAVITY