Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 30, 2017, 10:17 AM
  • B 1163_B 1162 _30062017_031732.mp4

Date
06/30/2017
W/O
640678
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01125
PipeID
P13483
Time
3:17 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4634
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
SOUTH PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
WO_640678_TV16072_JUN2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
B 1163
Downstream MH
B 1162
Dir. of Survey
Downstream
Length Surveyed
482.5 ft.
Total Length
482.6 ft.
Structural Index
3
Structural Quick
3400
Structural Rating
12
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole B 1163 to B 1162
MH: B 1163MH: B 1162downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 11630 ft. MWL - Water Level, 5 %of cross sectional area18.3 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"30.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"41.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"65.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"83.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"94.1 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"117.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"131.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"143.6 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES146.6 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES149 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES157.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"158.1 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"173 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"183.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"199.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"227.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"275.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"319.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"319.5 ft. RFL - Roots Fine Lateral, at 02 o'clock322.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"340.9 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES422 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"441.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"465.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"478.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"482.6 ft. AMH - Downstream Manhole, Survey Ends - B 1162

Observation photos (9)

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    41.7 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    94.1 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    143.6 ft. - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    146.6 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    149 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    158.1 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    183.2 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    340.9 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    441.6 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (30)

DistanceCodeObservation
94.1TB
322.3TF
0MWM
183.2TB
465.1TF
65.7TFC
441.6TB
143.6CM
41.7TB
146.6CM
422TFC
173TFC
83.2TFC
18.3TFA
0AMHB 1163
319.5TF
0MWL
319.5RFL
275.7TF
117.7TF
157.2TF
149CM
131.4TF
158.1TB
227.9TFC
30.5TFC
199.5TF
340.9CM
482.6AMHB 1162
478.2TF

Properties (5)

additional_info
SC345426
custom_field_two
4
customer
LACSD
datetime
2017-06-30T03:17:14-07:00
sewer_category
Gravity