Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 6, 2017, 07:58 AM
  • B 1135_B 1134_06072017_005828.mp4

Date
07/06/2017
W/O
640678
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01125
PipeID
P13175
Time
12:58 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4635
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
ALHAMBRA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
WO_640678_TV16072_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
B 1134
Downstream MH
B 1135
Dir. of Survey
Upstream
Length Surveyed
269 ft.
Total Length
269 ft.
Structural Index
3
Structural Quick
3D22
Structural Rating
79
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
81
Pipe schematic from manhole B 1134 to B 1135
MH: B 1134MH: B 1135upstream0 ft. AMH - Upstream Manhole, Survey Ends - B 11353.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish3.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"31.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"42.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"53.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"72.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"95.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"97.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"120.5 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"127.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start132 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"139.1 ft. RFJ - Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YES142.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"158.2 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES165.4 ft. RFJ - Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish170.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"178.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"209.4 ft. RFJ - Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YES, Start214.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"218.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"221.3 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES237.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"251.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"263.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"269 ft. MWL - Water Level, 5 %of cross sectional area269 ft. AMH - Downstream Manhole, Survey Begins - B 1134269 ft. MWM - Water Mark, 5 %of cross sectional area

Observation photos (7)

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    47.7 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    59.6 ft. - Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    110.8 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YES

    129.9 ft. - Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    141.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    148.5 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    173.2 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (28)

DistanceCodeObservation
126.5TFC
237.7TFC
196.5TF
31.6TFC
141.2CM
0MWL
215.8TF
47.7CL
269AMHB 1135
226.4TFC
137TFC
110.8CL
98.4TF
129.9RFJ
0AMHB 1134
103.6RFJ
265.5CM
173.2TB
148.5TB
54.2TF
90.7TF
59.6RFJ
5.9TF
17.2TF
171.8TF
265.5TFA
0MWM
50.5TF

Properties (4)

additional_info
SC345428
custom_field_two
3
customer
LACSD
datetime
2017-07-06T00:58:06-07:00