Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 6, 2017, 05:09 AM
  • B 1162_B 1161 _05072017_221203.mp4

Date
07/05/2017
W/O
640678
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01125
PipeID
P13482
Time
10:09 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4635
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
SOUTH PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
WO_640678_TV16072_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
B 1162
Downstream MH
B 1161
Dir. of Survey
Downstream
Length Surveyed
433.8 ft.
Total Length
433.8 ft.
Structural Index
3
Structural Quick
3J22
Structural Rating
172
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
172
Pipe schematic from manhole B 1162 to B 1161
MH: B 1162MH: B 1161downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 11620 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area45.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"47.3 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"57 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"89.6 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES95.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"100.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"118.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES142.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES145.4 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"156.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"158.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start190.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"192 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"204.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"227.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"250.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"294.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"306.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"312.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"342.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"352.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"357.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"369 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"376 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"401.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"433.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish433.8 ft. AMH - Downstream Manhole, Survey Ends - B 1161

Observation photos (5)

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    89.6 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    118.1 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    142.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    158.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    190.3 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (30)

DistanceCodeObservation
433.8CM
100.2TF
118.1CL
312.5TF
352.1TF
0AMHB 1162
433.8AMHB 1161
250.9TF
204.9TFC
142.2CM
89.6CL
227.6TF
306.6TFC
369TF
357.9TFC
156.7TF
192TF
57TFC
95.7TF
376TFC
294.3TF
190.3TB
45.2TF
342.3TF
401.3TF
145.4TF
0MWM
47.3TF
158.2CM
0MWL

Properties (4)

additional_info
SC345428
custom_field_two
3