Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 1, 2017, 09:30 AM
  • 08 0466_08 0465_912017_024102.mp4

Date
09/01/2017
W/O
0660368
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00026
PipeID
P00522
Time
2:30 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Heavy Cleaning
Media Label
H0633
Sewer Name
08 216TH STREET TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Maintenance Related
Project
20170901MDM_216TH_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
36 in.
Upstream MH
08 0466
Downstream MH
08 0465
Dir. of Survey
Downstream
Length Surveyed
343.7 ft.
Total Length
343.7 ft.
Structural Index
5
Structural Quick
5300
Structural Rating
15
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
19
Pipe schematic from manhole 08 0466 to 08 0465
MH: 08 0466MH: 08 0465downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:30AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MISSING, BROKEN REBAR2 ft. MGO - General Observation - 36" RCP- CTL13.8 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR34.8 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR100.2 ft. MGO - General Observation - 36" RCP-CTL218.1 ft. MGO - General Observation - 36" RCP-CTL305.4 ft. MGP - General Photograph343.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - MISSING ,BROKEN REBAR343.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active343.7 ft. AMH - Downstream Manhole, Survey Ends - 2:55AM

Observation photos (7)

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MISSING, BROKEN REBAR

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MISSING, BROKEN REBAR

  • General Observation - 36" RCP- CTL

    2 ft. - General Observation - 36" RCP- CTL

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR

    13.8 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

    34.8 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

  • General Observation - 36" RCP-CTL

    100.2 ft. - General Observation - 36" RCP-CTL

  • General Observation - 36" RCP-CTL

    218.1 ft. - General Observation - 36" RCP-CTL

  • General Photograph

    305.4 ft. - General Photograph

Observations (14)

DistanceCodeObservation
0AMH2:30AM
343.7AMH2:55AM
100.2MGO36" RCP-CTL
343.3SRCMISSING ,BROKEN REBAR
0MWL
2SRCMISSING, BROKEN REBAR
2MGO36" RCP- CTL
305.4MGP
0MGOConn. @ Mh, 3 O' Clock. OPEN
343.3MGOConn. @ Mh, 3 O' Clock. Active
34.8SRCHANGING REBAR
13.8SRCBROKEN MISSING REBAR
218.1MGO36" RCP-CTL
0MWM

Properties (4)

custom_field_three
MISSING BROKEN REBAR
custom_field_two
1
customer
LACSD
datetime
2017-09-01T02:30:00-07:00