Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 6, 2017, 06:59 AM
  • 05 2574_05 2573 _06062017_001329.mp4

Date
06/05/2017
W/O
641198
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01131
PipeID
P25276
Time
11:59 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3962
Sewer Name
05 COLDEN AVENUE RELIEF TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_641198_TV05127_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 2574
Downstream MH
05 2573
Dir. of Survey
Downstream
Length Surveyed
401.1 ft.
Total Length
401.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 05 2574 to 05 2573
MH: 05 2574MH: 05 2573downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 25740 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start399.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish401.1 ft. AMH - Downstream Manhole, Survey Ends - 05 2573

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
401.1AMH05 2573
0AMH05 2574
2.4DAGS
0MWM
0MWL
399.1DAGS

Properties (4)

custom_field_two
4
customer
LACSD
datetime
2017-06-05T23:59:54-07:00
year_laid
38590