Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 19, 2017, 07:15 AM
  • 02 1546_02 1545B_19072017_002030.mp4

Date
07/19/2017
W/O
646606
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00230
PipeID
P03977
Time
12:15 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4653
Sewer Name
02 ARIZONA AVENUE TRUNK, SECTION 1
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_646606_TV02006_JUL2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 1545B
Downstream MH
02 1546
Dir. of Survey
Upstream
Length Surveyed
12.6 ft.
Total Length
12.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3121
O&M Rating
9
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 02 1545B to 02 1546
MH: 02 1545BMH: 02 1546upstream0 ft. MSA - Survey Abandoned - CAM BLKD BY ROOTS0 ft. RMC - Roots Medium Connection, from 08 to 10 o'clock, 20 %, within 8 inches of joint: NO0 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6"0.9 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES3.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES3.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES10 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES12.7 ft. AMH - Downstream Manhole, Survey Begins - 02 1545B12.7 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK12.7 ft. MWL - Water Level, 10 %of cross sectional area12.7 ft. MWM - Water Mark, 15 %of cross sectional area

Observation photos (6)

  • Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES

    2.7 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

    9.1 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

    9.1 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

    11.8 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Roots Medium Connection, from 08 to 10 o'clock, 20 %, within 8 inches of joint: NO

    12.7 ft. - Roots Medium Connection, from 08 to 10 o'clock, 20 %, within 8 inches of joint: NO

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    12.7 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (11)

DistanceCodeObservation
9.1RFJ
2.7RFJ
0AMH02 1545B
12.7MSACAM BLKD BY ROOTS
11.8RFJ
12.7RMC
0MGOCONNECTION AT MH 3 O'CLOCK
12.7TFD
0MWL
0MWM
9.1RFJ

Properties (5)

additional_info
SC345513
custom_field_two
3
customer
LACSD
datetime
2017-07-19T00:15:00-07:00
sewer_category