Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 19, 2017, 06:21 AM
  • 02 1546A_02 1546_18072017_232237.mp4

Date
07/18/2017
W/O
646606
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00230
PipeID
P03978
Time
11:21 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4653
Sewer Name
02 ARIZONA AVENUE TRUNK, SECTION 1
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_646606_TV02006_JUL2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 1546A
Downstream MH
02 1546
Dir. of Survey
Downstream
Length Surveyed
137.6 ft.
Total Length
137.6 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
39
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
40
Pipe schematic from manhole 02 1546A to 02 1546
MH: 02 1546AMH: 02 1546downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 1546A0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK24.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"47.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"50 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"71.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start91.4 ft. RFJ - Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YES94.9 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"103.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"137.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish137.6 ft. AMH - Downstream Manhole, Survey Ends - 02 1546

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    71.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    94.9 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

Observations (14)

DistanceCodeObservation
71.5CM
137.6CM
47.1TFC
0MWM
137.6AMH02 1546
0MGOCONNECTION AT MH 3 O'CLOCK
50TFC
0MWL
94.9TB
103.7TB
24.5TFC
0AMH02 1546A
91.4RFJ
0MGOCONNECTION AT MH 9 O'CLOCK

Properties (5)

additional_info
SC345513
custom_field_two
3
customer
LACSD
datetime
2017-07-18T23:21:57-07:00
sewer_category
Gravity