Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 28, 2017, 10:12 AM
  • H 0869_H 0489A_072817_031256.mp4

Date
07/28/2017
W/O
646501
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00181
PipeID
P20460
Time
3:12 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4673
Sewer Name
H JOINT OUTFALL H - UNIT 6
City
CITY OF INDUSTRY
Loc. details
Railway
Location Code
L
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
WO_646501_TV15212_JUL2017
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
H 0869
Downstream MH
H 0489A
Dir. of Survey
Downstream
Length Surveyed
357.8 ft.
Total Length
357.8 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
210
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
3
Overall Quick
Overall Rating
350
Pipe schematic from manhole H 0869 to H 0489A
MH: H 0869MH: H 0489Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - H 08690 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area6.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.5 ft. MGO - General Observation - MAG COATING80.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 8"357.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish357.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish357.8 ft. AMH - Downstream Manhole, Survey Ends - H 0489A

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    6.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
6.4DAGS
357.8SAV
357.8DAGS
0AMHH 0869
80.8TF
0MWM
6.5MGOMAG COATING
0MWL
6.4SAV
357.8AMHH 0489A

Properties (5)

additional_info
SC345611
custom_field_two
3
customer
LACSD
datetime
2017-07-28T03:12:23-07:00
sewer_category
Gravity