Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 2, 2017, 07:15 AM
Date
06/02/2017
W/O
641198
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z01131
PipeID
P25292
Time
12:15 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4274
Sewer Name
05 COLDEN AVENUE RELIEF TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_641198_TV05127_JUN2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 2588
Downstream MH
05 2587
Dir. of Survey
Downstream
Length Surveyed
414.1 ft.
Total Length
414.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 05 2588 to 05 2587
MH: 05 2588MH: 05 2587downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 25882.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start411.6 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish414.1 ft. AMH - Downstream Manhole, Survey Ends - 05 2587

Observation photos (1)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
0MWM
0MWL
2.1DAGS
0AMH05 2588
414.1AMH05 2587
411.6DAGS

Properties (6)

additional_info
SC345278
custom_field_two
4
customer
LACSD
datetime
2017-06-02T00:15:30-07:00
sewer_category
Gravity
year_laid
38590