Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 17, 2017, 09:14 AM
  • 18 0885A_18 0885_20170517_022501.mp4

Date
05/17/2017
W/O
635479
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00709
PipeID
P14737
Time
2:14 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4498
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
WO_635479_TV18051_MAY2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0885A
Downstream MH
18 0885
Dir. of Survey
Downstream
Length Surveyed
175.5 ft.
Total Length
175.5 ft.
Structural Index
4
Structural Quick
5L3M
Structural Rating
539
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
539
Pipe schematic from manhole 18 0885A to 18 0885
MH: 18 0885AMH: 18 0885downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 0885A2.7 ft. SRV - Surface Reinforcement Visible, from 03 to 05 o'clock, within 8 inches of joint: YES, Start2.7 ft. SAP - Surface Aggregate Projecting, from 03 to 05 o'clock, within 8 inches of joint: YES, Start9.3 ft. SAP - Surface Aggregate Projecting, from 07 to 09 o'clock, within 8 inches of joint: YES, Start14.4 ft. SRV - Surface Reinforcement Visible, from 07 to 09 o'clock, within 8 inches of joint: YES, Start175.5 ft. SAP - Surface Aggregate Projecting, from 03 to 05 o'clock, within 8 inches of joint: YES, Finish175.5 ft. SRV - Surface Reinforcement Visible, from 07 to 09 o'clock, within 8 inches of joint: YES, Finish175.5 ft. SRV - Surface Reinforcement Visible, from 03 to 05 o'clock, within 8 inches of joint: YES, Finish175.5 ft. SAP - Surface Aggregate Projecting, from 07 to 09 o'clock, within 8 inches of joint: YES, Finish175.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0885

Observation photos (4)

  • Surface Reinforcement Visible, from 03 to 05 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Surface Reinforcement Visible, from 03 to 05 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 03 to 05 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Surface Aggregate Projecting, from 03 to 05 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 07 to 09 o'clock, within 8 inches of joint: YES, Start

    9.3 ft. - Surface Aggregate Projecting, from 07 to 09 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 07 to 09 o'clock, within 8 inches of joint: YES, Start

    14.4 ft. - Surface Reinforcement Visible, from 07 to 09 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
2.7SRV
175.5SAP
9.3SAP
0MWL
2.7SAP
175.5SRV
175.5SRV
0MGOCONNECTION AT MH 9 O'CLOCK
175.5SAP
175.5AMH18 0885
0MWM
14.4SRV
0AMH18 0885A

Properties (4)

additional_info
SC345307
custom_field_two
2
customer
LACSD
datetime
2017-05-17T02:14:58-07:00