Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 17, 2017, 09:48 AM
  • 18 0885_18 0884 _20170517_030753.mp4

Date
05/17/2017
W/O
635479
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00709
PipeID
P14736
Time
2:48 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4498
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
WO_635479_TV18051_MAY2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0885
Downstream MH
18 0884
Dir. of Survey
Downstream
Length Surveyed
600.7 ft.
Total Length
600.7 ft.
Structural Index
4
Structural Quick
5o3o
Structural Rating
1904
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
1904
Pipe schematic from manhole 18 0885 to 18 0884
MH: 18 0885MH: 18 0884downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 08856.5 ft. SAP - Surface Aggregate Projecting, from 03 to 05 o'clock, within 8 inches of joint: YES, Start6.5 ft. SAP - Surface Aggregate Projecting, from 07 to 09 o'clock, within 8 inches of joint: YES, Start6.5 ft. SRV - Surface Reinforcement Visible, from 03 to 05 o'clock, within 8 inches of joint: YES, Start6.5 ft. SRV - Surface Reinforcement Visible, from 07 to 09 o'clock, within 8 inches of joint: YES, Start600.7 ft. SAP - Surface Aggregate Projecting, from 07 to 09 o'clock, within 8 inches of joint: YES, Finish600.7 ft. SRV - Surface Reinforcement Visible, from 07 to 09 o'clock, within 8 inches of joint: YES, Finish600.7 ft. SAP - Surface Aggregate Projecting, from 03 to 05 o'clock, within 8 inches of joint: YES, Finish600.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK600.7 ft. SRV - Surface Reinforcement Visible, from 03 to 05 o'clock, within 8 inches of joint: YES, Finish600.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0884

Observation photos (4)

  • Surface Aggregate Projecting, from 03 to 05 o'clock, within 8 inches of joint: YES, Start

    6.5 ft. - Surface Aggregate Projecting, from 03 to 05 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 07 to 09 o'clock, within 8 inches of joint: YES, Start

    6.5 ft. - Surface Aggregate Projecting, from 07 to 09 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 03 to 05 o'clock, within 8 inches of joint: YES, Start

    6.5 ft. - Surface Reinforcement Visible, from 03 to 05 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 07 to 09 o'clock, within 8 inches of joint: YES, Start

    6.5 ft. - Surface Reinforcement Visible, from 07 to 09 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0MWL
0MWM
6.5SAP
600.7SAP
600.7SRV
600.7SAP
600.7MGOCONNECTION AT MH 9 O'CLOCK
6.5SAP
6.5SRV
6.5SRV
600.7SRV
0AMH18 0885
600.7AMH18 0884

Properties (4)

additional_info
SC345307
custom_field_two
2
customer
LACSD
datetime
2017-05-17T02:48:14-07:00