Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 6, 2016, 06:18 AM
  • H 0572_H 0571_05052016_231923.mp4

Date
05/05/2016
W/O
568671
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00188
PipeID
P10996
Time
11:18 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3341
Sewer Name
H JOINT OUTFALL H - UNIT 8E
City
BALDWIN PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
19
Purpose
Routine Assessment
Project
WO_568671_TV15173_MAY2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
H 0572
Downstream MH
H 0571
Dir. of Survey
Downstream
Length Surveyed
329.1 ft.
Total Length
329.1 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
325
O&M Index
2
O&M Quick
412L
O&M Rating
138
Overall Index
2
Overall Quick
Overall Rating
463
Pipe schematic from manhole H 0572 to H 0571
MH: H 0572MH: H 0571downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK.0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 05720 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start15.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"48.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"56.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"105 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS129.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"137.3 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS152.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"185.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"218.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"234.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"264.9 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"274.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"290.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"328 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish328 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish328 ft. MGO - General Observation - COCKROACHES IN MANHOLE328 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish329.1 ft. AMH - Downstream Manhole, Survey Ends - H 0571

Observation photos (7)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    105 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    137.3 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • General Observation - COCKROACHES IN MANHOLE

    328 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (26)

DistanceCodeObservation
274.6TFC
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK.
129.2TFA
15.4TFA
328SSS
185.7TFA
48.1TFA
218.3TFA
2SAV
105TFDROOTS
328DAGS
329.1AMHH 0571
56.2TFC
137.3TFDROOTS
328MGOCOCKROACHES IN MANHOLE
152.9TFC
2SSS
0MWL
0MWM
264.9TBA
0AMHH 0572
328SAV
2DAGS
0MGOCOCKROACHES IN MANHOLE
290.7TFA
234.3TFC

Properties (4)

additional_info
SC305618
custom_field_two
3
customer
LACSD
datetime
2016-05-05T23:18:33-07:00