Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 21, 2017, 06:50 AM
  • 02 1225_02 1224_20072017_235058.mp4

Date
07/20/2017
W/O
646745
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00303
PipeID
P03728
Time
11:50 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4756
Sewer Name
02 SANTA ANITA OUTFALL TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
14
Purpose
Routine Assessment
Project
WO_646745_TV02120_JUL2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
02 1225
Downstream MH
02 1224
Dir. of Survey
Downstream
Length Surveyed
432.3 ft.
Total Length
432.3 ft.
Structural Index
3
Structural Quick
3D24
Structural Rating
86
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
86
Pipe schematic from manhole 02 1225 to 02 1224
MH: 02 1225MH: 02 1224downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 6 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 12250 ft. MWL - Water Level, 10 %of cross sectional area16.5 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES21.2 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES33.4 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES52 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES59.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES61.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start69.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"179.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"186.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish272.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"278.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"329.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"414.6 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"432.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK432.3 ft. AMH - Downstream Manhole, Survey Ends - 02 1224

Observation photos (11)

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    16.5 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    21.2 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    33.4 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    52 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    59.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    61.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    69.6 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    179.1 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    272.9 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    278.3 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    414.6 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (19)

DistanceCodeObservation
52CL
69.6TB
0MWM
61.9CM
272.9TB
329.7TFA
432.3MGOCONNECTION AT MH 3 O'CLOCK
16.5CL
33.4CL
414.6TS
432.3AMH02 1224
0MGOCONNECTION AT MH 6 O'CLOCK
0AMH02 1225
278.3TB
59.2CM
186.4CM
0MWL
21.2CL
179.1TBA

Properties (5)

additional_info
SC345516
custom_field_two
3
customer
LACSD
datetime
2017-07-20T23:50:31-07:00
sewer_category
Gravity