Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 27, 2016, 08:56 AM
  • 18 0033_18 0032_042716_015736.mpg

Date
04/27/2016
W/O
568736
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00713
PipeID
P13849
Time
1:56 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3330
Sewer Name
18 WALNUT WAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
15
Purpose
Routine Assessment
Project
WO_568736_TV18059_MAY2016
Material
NRCP
Shape
Circular
Height
12 in.
Upstream MH
18 0033
Downstream MH
18 0032
Dir. of Survey
Downstream
Length Surveyed
318.3 ft.
Total Length
318.3 ft.
Structural Index
3
Structural Quick
3L22
Structural Rating
201
O&M Index
1
O&M Quick
1800
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
209
Pipe schematic from manhole 18 0033 to 18 0032
MH: 18 0033MH: 18 0032downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00330 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.3 ft. MGO - General Observation - MAG COAT 25%10.7 ft. CM - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES15.8 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 4"30.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"53.7 ft. CC - Crack Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES61.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"72.1 ft. CC - Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES82.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"89.6 ft. RFJ - Roots Fine Joint, from 07 to 08 o'clock, within 8 inches of joint: YES89.6 ft. RFJ - Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES96.5 ft. RFJ - Roots Fine Joint, at 05 o'clock, within 8 inches of joint: YES106.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES114.4 ft. RFJ - Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES, Start119.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"120.6 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"139 ft. RFJ - Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES, Finish194.2 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES205 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"243.5 ft. CL - Crack Longitudinal, at 07 o'clock, within 8 inches of joint: YES284.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"299.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"314.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"315 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish318.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0032

Observation photos (9)

  • Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    10.7 ft. - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES

    53.7 ft. - Crack Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

    72.1 ft. - Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 07 to 08 o'clock, within 8 inches of joint: YES

    89.6 ft. - Roots Fine Joint, from 07 to 08 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES

    89.6 ft. - Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 05 o'clock, within 8 inches of joint: YES

    96.5 ft. - Roots Fine Joint, at 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    106.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    194.2 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 07 o'clock, within 8 inches of joint: YES

    243.5 ft. - Crack Longitudinal, at 07 o'clock, within 8 inches of joint: YES

Observations (29)

DistanceCodeObservation
120.6TF
89.6RFJ
89.6RFJ
114.4RFJ
139RFJ
315SAV
205TF
194.2CL
15.8TB
318.3AMH18 0032
61.4TFC
72.1CC
119.6TFC
10.7CM
314.8TF
0AMH18 0033
82.6TFC
2SAV
0MWM
106.1CM
53.7CC
2.3MGOMAG COAT 25%
299.5TFC
0MWL
0MGOCONNECTION AT MH 3 OCLOCK
243.5CL
284.3TF
96.5RFJ
30.6TFC

Properties (5)

additional_info
SC226000
custom_field_two
3
customer
LACSD
datetime
2016-04-27T01:56:59-07:00
sewer_category