Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 30, 2017, 03:38 PM
  • Section#1_05 2615_05 2614__8302017__G6812.mp4

Date
08/30/2017
W/O
0651131
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z01145
PipeID
P25706
Time
8:38 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Jetting
Media Label
G6812
Sewer Name
05 MANCHESTER AVENUE PUMP RELIEF TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Maintenance Related
Project
20170830SHO_MANCHESTER_AVENUE_PUMP_RELIEF_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
36 in.
Upstream MH
05 2615
Downstream MH
05 2614
Dir. of Survey
Downstream
Length Surveyed
304.7 ft.
Total Length
304.7 ft.
Structural Index
2
Structural Quick
2K00
Structural Rating
122
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
126
Pipe schematic from manhole 05 2615 to 05 2614
MH: 05 2615MH: 05 2614downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08450 ft. MWL - Water Level, 40 %of cross sectional area0.7 ft. MWM - Water Mark, 55 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start304.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish304.7 ft. MSA - Survey Abandoned - TOO MUCH DEBRIS

Observation photos (1)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
304.7SSS
2SSS
304.7MSATOO MUCH DEBRIS
0AMH0845
0.7MWM
0MWL

Properties (5)

additional_info
LOOKING FOR DAMAGE TO THE CROWN OF THE PIPE
custom_field_three
EMERGENCY CCTV, NOT A FULL INSPECTION
custom_field_two
1
customer
LACSD
datetime