Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 31, 2017, 08:26 AM
Date
05/31/2017
W/O
641198
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z01131
PipeID
P25298
Time
1:26 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4273
Sewer Name
05 COLDEN AVENUE RELIEF TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_641198_TV05127_JUN2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 2593
Downstream MH
05 2592
Dir. of Survey
Downstream
Length Surveyed
357.4 ft.
Total Length
357.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 05 2593 to 05 2592
MH: 05 2593MH: 05 2592downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 25930.2 ft. MWM - Water Mark, 20 %of cross sectional area2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start353.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish357.4 ft. AMH - Downstream Manhole, Survey Ends - 05 2592

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
0MWL
357.4AMH05 2592
0AMH05 2593
2.2DAGS
353.6DAGS
0.2MWM

Properties (6)

additional_info
SC345273
custom_field_two
4
customer
LACSD
datetime
2017-05-31T01:26:54-07:00
sewer_category
Gravity
year_laid
38590