- Date
- 08/02/2017
- W/O
- 0653438
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00677
- PipeID
- P14878
- Time
- 12:50 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Heavy Cleaning
- Media Label
- G6787
- Sewer Name
- 18 LA HABRA HEIGHTS TRUNK, SECTION 1
- City
- LA HABRA
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 22
- Purpose
- Routine Assessment
- Project
- 20170801MDM_LA_HABRA_HEIGHTS_TRUNK_SECTION_1
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 7.559999942779541 in.
- Upstream MH
- 18 1023
- Downstream MH
- 18 1024
- Dir. of Survey
- Upstream
- Length Surveyed
- 268.6 ft.
- Total Length
- 268.7 ft.
- Structural Index
- 0
- Structural Quick
- 0000
- Structural Rating
- 0
- O&M Index
- 3
- O&M Quick
- 4B3I
- O&M Rating
- 245
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 245
Pipe schematic from manhole 18 1023 to 18 1024 Observation photos (3)

8 ft. - General Observation - 8" VCP - CIPP

68.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

158.7 ft. - Deposits Attached Grease, 20 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: NO