- Date
- 07/17/2017
- W/O
- 641001
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00055
- PipeID
- P11434
- Time
- 1:25 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K4709
- Sewer Name
- J JOINT OUTFALL J - UNIT 1C
- City
- SAN PEDRO
- Loc. details
- Main Highway - Suburban/Rural
- Location Code
- B
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 48
- Purpose
- Routine Assessment
- Project
- WO_641001_TV05283_JUN2017
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 27 in.
- Width
- 27 in.
- Upstream MH
- J 0407
- Downstream MH
- J 0194
- Dir. of Survey
- Downstream
- Length Surveyed
- 362.8 ft.
- Total Length
- 362.8 ft.
- Structural Index
- 3
- Structural Quick
- 3B00
- Structural Rating
- 42
- O&M Index
- 2
- O&M Quick
- 2\00
- O&M Rating
- 286
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 328
Pipe schematic from manhole J 0407 to J 0194 Observation photos (3)

8.2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

263.7 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

304.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start