Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 8, 2017, 08:46 AM
  • 18 0206_18 0205 _20170308_020142.mp4

Date
03/08/2017
W/O
624437
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00695
PipeID
P14031
Time
12:46 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4313
Sewer Name
18 ORR AND DAY ROAD TRUNK
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_624437_TV18043_MAR2017
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0206
Downstream MH
18 0205
Dir. of Survey
Downstream
Length Surveyed
299.1 ft.
Total Length
299.1 ft.
Structural Index
3
Structural Quick
3K2H
Structural Rating
265
O&M Index
3
O&M Quick
413K
O&M Rating
299
Overall Index
3
Overall Quick
Overall Rating
564
Pipe schematic from manhole 18 0206 to 18 0205
MH: 18 0206MH: 18 0205downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02060 ft. MWM - Water Mark, 60 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS78.9 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start299.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish299.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK299.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE299.1 ft. AMH - Downstream Manhole, Survey Ends - 18 0205299.1 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish299.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish299.1 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    78.9 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    299.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (15)

DistanceCodeObservation
2SAV
299.1DAGS
299.1MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MGOCOCKROACHES IN MANHOLE
299.1MGOCOCKROACHES IN MANHOLE
2DAGS
299.1AMH18 0205
0MWL
2DSZDEBRIS
78.9SSS
0AMH18 0206
299.1DSZ
299.1SAV
0MWM
299.1SSS

Properties (5)

additional_info
SC306966
custom_field_two
2
customer
LACSD
datetime
2017-03-08T00:46:54-08:00
sewer_category
Gravity