Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 23, 2017, 08:17 AM
  • 05 1878_05 1877_8232017_014042.mp4

Date
08/23/2017
W/O
0652018
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00507
PipeID
P07103
Time
1:17 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0620
Sewer Name
05 NARBONNE AVENUE TRUNK, SECTION 1(WEST)
City
LOMITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
35
Purpose
Routine Assessment
Project
20170822MDM_NARBONNE_AVENUE_TRUNK_SECTION_1_WEST
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
05 1878
Downstream MH
05 1877
Dir. of Survey
Downstream
Length Surveyed
349.5 ft.
Total Length
349.5 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 05 1878 to 05 1877
MH: 05 1878MH: 05 1877downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:35AM0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area8 ft. MGO - General Observation - 8" VCP48.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active75.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped123 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active146.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped166 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE192.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open201.3 ft. MGO - General Observation - 8" VCP236.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped263.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active326.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open345.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open348.5 ft. FC - Fracture Circumferential, from 07 to 06 o'clock, within 8 inches of joint: YES - HAIRLINE349.5 ft. AMH - Downstream Manhole, Survey Ends - 2:15AM

Observation photos (2)

  • General Observation - 8" VCP

    8 ft. - General Observation - 8" VCP

  • General Observation - 8" VCP

    201.3 ft. - General Observation - 8" VCP

Observations (17)

DistanceCodeObservation
0AMH1:35AM
348.5FCHAIRLINE
0MWL
263.4TFActive
192.3TBOpen
349.5AMH2:15AM
345.5TFOpen
0MWM
146.3TFCCapped
123TFActive
201.3MGO8" VCP
48.5TFActive
75.1TFCCapped
166FLHAIRLINE
8MGO8" VCP
236.7TFCCapped
326.6TFOpen

Properties (3)

custom_field_two
4
customer
LACSD
datetime
2017-08-23T01:17:58-07:00