- Date
- 08/22/2017
- W/O
- 0635578
- Weather
- Dry
- Operator/Surveyor
- SANTIAGO OBREGON
- Sewer ID
- Z00168
- PipeID
- P10632
- Time
- 9:05 AM
- Certificate
- U-1014-06022541
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G7499
- Sewer Name
- H JOINT OUTFALL H - UNIT 2B
- City
- BELL GARDENS
- Loc. details
- Main Highway - Suburban/Rural
- Location Code
- B
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 23
- Purpose
- Routine Assessment
- Project
- 20170821SHO_JOINT_OUTFALL_H_UNIT_2B
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 39 in.
- Upstream MH
- H 0183
- Downstream MH
- H 0062
- Dir. of Survey
- Downstream
- Length Surveyed
- 635.4 ft.
- Total Length
- 635.4 ft.
- Structural Index
- 3
- Structural Quick
- 5131
- Structural Rating
- 10
- O&M Index
- 3
- O&M Quick
- 4122
- O&M Rating
- 8
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 18
Pipe schematic from manhole H 0183 to H 0062 Observation photos (4)

8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

8.1 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

8.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

494.7 ft. - Surface Spalling, from 10 to 11 o'clock, within 8 inches of joint: NO