Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 22, 2017, 04:04 PM
  • H 0184_H 0183_8222017_091753.mp4

Date
08/22/2017
W/O
0635578
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00168
PipeID
P20082
Time
9:04 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7499
Sewer Name
H JOINT OUTFALL H - UNIT 2B
City
BELL GARDENS
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
20170821SHO_JOINT_OUTFALL_H_UNIT_2B
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Upstream MH
H 0184
Downstream MH
H 0183
Dir. of Survey
Downstream
Length Surveyed
589.6 ft.
Total Length
589.6 ft.
Structural Index
5
Structural Quick
5631
Structural Rating
33
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
4
Overall Quick
Overall Rating
39
Pipe schematic from manhole H 0184 to H 0183
MH: H 0184MH: H 0183downstream0 ft. AMH - Upstream Manhole, Survey Begins - 09150 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area8 ft. MGO - General Observation - SMALL RIBCAGE EFFECT 11 TO 1 O CLOCK8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start8.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start69.8 ft. MGO - General Observation - 70% MAG COAT87.4 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - POSSIBLE REBAR121.9 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES135.9 ft. SRV - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES, Start157.1 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start157.1 ft. SRV - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES, Finish518.4 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish539.9 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO563.8 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, Start583.5 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, Finish583.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish583.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish589.6 ft. AMH - Downstream Manhole, Survey Ends - 0950

Observation photos (9)

  • General Observation - SMALL RIBCAGE EFFECT 11 TO 1 O CLOCK

    8 ft. - General Observation - SMALL RIBCAGE EFFECT 11 TO 1 O CLOCK

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    8.5 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - 70% MAG COAT

    69.8 ft. - General Observation - 70% MAG COAT

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - POSSIBLE REBAR

    87.4 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - POSSIBLE REBAR

  • Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES

    121.9 ft. - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES, Start

    135.9 ft. - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    157.1 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

    539.9 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, Start

    563.8 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, Start

Observations (19)

DistanceCodeObservation
0AMH0915
583.5SRV
157.1SRV
0MWM
589.6AMH0950
518.4SRV
157.1SRV
8.5SAP
539.9SRV
69.8MGO70% MAG COAT
563.8SRV
583.5DAGS
583.5SAP
135.9SRV
121.9SRV
0MWL
8MGOSMALL RIBCAGE EFFECT 11 TO 1 O CLOCK
87.4SRVPOSSIBLE REBAR
8DAGS

Properties (4)

custom_field_three
VISIBLE REBAR & PROJECTING AGG.
custom_field_two
2
customer
LACSD
datetime
2017-08-22T09:04:14-07:00