Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 18, 2017, 08:26 AM
  • Section#1_D 0162_D 0161__8182017__G6806.mp4

Date
08/18/2017
W/O
0647700
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00157
PipeID
P10038
Time
1:26 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6806
Sewer Name
D JOINT OUTFALL D - UNIT 6 RELIEF
City
HAWTHORNE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
20170818MDM_JOINT_OUTFALL_UNIT_6_RELIEF
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Upstream MH
D 0162
Downstream MH
D 0161
Dir. of Survey
Downstream
Length Surveyed
348.8 ft.
Total Length
348.8 ft.
Structural Index
3
Structural Quick
513M
Structural Rating
349
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
354
Pipe schematic from manhole D 0162 to D 0161
MH: D 0162MH: D 0161downstream0 ft. MGO - General Observation - MH CONN 3:00 ACTIVE0 ft. MWL - Water Level, 60 %of cross sectional area0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:30AM2 ft. MGO - General Observation - 98% MAG COAT 10:00 TO 2:00 START2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE10.7 ft. SAV - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG14.7 ft. SAV - Surface Aggregate Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - SEVERE AGG27.1 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT27.1 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG96.8 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CVIRCUM REBAR148.6 ft. SAV - Surface Aggregate Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG303.2 ft. MGP - General Photograph334.2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - PEELING CONCRETE348.2 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG348.2 ft. MGO - General Observation - MH CONN 3:00 STUB348.2 ft. MGO - General Observation - 98% MAG COAT FINISH348.2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE UNDER MAG COAT348.2 ft. MGO - General Observation - MH CONN 9:00 ACTIVE348.8 ft. AMH - Downstream Manhole, Survey Ends - 2:00AM

Observation photos (10)

  • General Observation - 98% MAG COAT 10:00 TO 2:00 START

    2 ft. - General Observation - 98% MAG COAT 10:00 TO 2:00 START

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

    10.7 ft. - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - SEVERE AGG

    14.7 ft. - Surface Aggregate Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT

    27.1 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    27.1 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CVIRCUM REBAR

    96.8 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CVIRCUM REBAR

  • Surface Aggregate Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    148.6 ft. - Surface Aggregate Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Photograph

    303.2 ft. - General Photograph

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    334.2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

Observations (20)

DistanceCodeObservation
303.2MGP
348.8AMH2:00AM
27.1SAVSEVERE AGG UNDER MAG COAT
334.2SSSPEELING CONCRETE
348.2SAVSEVERE AGG
27.1SAVSEVERE AGG
2MGO98% MAG COAT 10:00 TO 2:00 START
96.8SRVCVIRCUM REBAR
348.2MGOMH CONN 3:00 STUB
0MGOMH CONN 3:00 ACTIVE
2SSSBLISTERING PEELING CONCRETE
348.2MGO98% MAG COAT FINISH
10.7SAVSEVERE AGG
348.2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
0MWL
14.7SAVSEVERE AGG
348.2MGOMH CONN 9:00 ACTIVE
0MWM
148.6SAVSEVERE AGG
0AMH1:30AM

Properties (5)

custom_field_three
CIRCUM REBAR VISIBLE
custom_field_two
2
customer
LACSD
datetime
2017-08-18T01:26:02-07:00
year_laid
19820204