Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 26, 2017, 09:27 AM
  • 01 0555_01 0554_26062017_033629.mp4

Date
06/26/2017
W/O
640684
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00206
PipeID
P01044
Time
2:27 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3975-SC342136
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
WO_640684_TV01243_JUN2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
01 0554
Downstream MH
01 0555
Dir. of Survey
Upstream
Length Surveyed
53.1 ft.
Total Length
53.1 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
2
O&M Quick
4129
O&M Rating
22
Overall Index
2
Overall Quick
Overall Rating
31
Pipe schematic from manhole 01 0554 to 01 0555
MH: 01 0554MH: 01 0555upstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 05550.9 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK2.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish2.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish19.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start33 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"46.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start53.1 ft. MWL - Water Level, 10 %of cross sectional area53.1 ft. AMH - Downstream Manhole, Survey Begins - 01 055453.1 ft. MWM - Water Mark, 50 %of cross sectional area

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    6.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    33.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
52.2MGOCONNECTION AT THE MH 3 O'CLOCK
53.1AMH01 0555
0MWL
0AMH01 0554
33.3CM
6.9DAGS
50.3CM
20.1TFC
50.3DAGS
0MWM

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2017-06-26T02:27:36-07:00