Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 11, 2017, 09:55 AM
  • 18 0014_18 0013 _11072017_025549.mp4

Date
07/11/2017
W/O
641208
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00713
PipeID
P13830
Time
2:55 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4640
Sewer Name
18 WALNUT WAY TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_641208_TV18059_JUN2017
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0014
Downstream MH
18 0013
Dir. of Survey
Downstream
Length Surveyed
223 ft.
Total Length
223 ft.
Structural Index
3
Structural Quick
413H
Structural Rating
136
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
136
Pipe schematic from manhole 18 0014 to 18 0013
MH: 18 0014MH: 18 0013downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 00140 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area2.1 ft. MGO - General Observation - MAG COAT3.7 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start46.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"66.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"101.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"121.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"148.2 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"152.6 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"178.8 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES210.4 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES212.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"221 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish223 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK223 ft. AMH - Downstream Manhole, Survey Ends - 18 0013

Observation photos (3)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    178.8 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    210.4 ft. - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
66.6TF
121.1TF
46.7TF
148.2TF
0MWM
223MGOCONNECTION AT MH 9 O'CLOCK
0AMH18 0014
223AMH18 0013
3.7SAV
152.6TF
210.4CM
101.3TF
0MGOCONNECTION AT MH 3 O'CLOCK
2.1MGOMAG COAT
178.8FM
0MWL
221SAV
212.7TF

Properties (5)

additional_info
SC345386
custom_field_two
3
customer
LACSD
datetime
2017-07-11T02:55:06-07:00
sewer_category
Gravity