Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2017, 09:37 AM
  • 02 0010_02 0009_21062017_035335.mp4

Date
06/21/2017
W/O
640701
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00234
PipeID
P03036
Time
2:37 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4623
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
WO_640701_TV02341_JUN2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
02 0010
Downstream MH
02 0009
Dir. of Survey
Downstream
Length Surveyed
383.2 ft.
Total Length
383.2 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 02 0010 to 02 0009
MH: 02 0010MH: 02 0009downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 00100 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area21.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"77.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"92.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES145 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"206.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"270.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"289.2 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES320.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"322 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES383.2 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK383.2 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK383.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0009

Observation photos (3)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    92.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    289.2 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    322 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
145TFA
320.2TFC
92.8CL
0AMH02 0010
21.3TF
0MWM
383.2MGOCONNECTION AT THE MH 3 O'CLOCK
322CL
206.5TF
0MWL
383.2MGOCONNECTION AT THE MH 9 O'CLOCK
270.2TF
383.2AMH02 0009
77.6TFA
289.2CL

Properties (5)

additional_info
SC345338
custom_field_two
3
customer
LACSD
datetime
2017-06-21T02:37:26-07:00
sewer_category
Gravity