02 0009_02 0008_21062017_041102.mp4
64.9 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES
94.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES
97.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

180.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES
191.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start
233.1 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start
252.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES
312.2 ft. - Roots Fine Lateral, at 12 o'clock
| Distance | Code | Observation |
|---|---|---|
| 312.2 | TF | — |
| 312.2 | RFL | — |
| 233.1 | CM | — |
| 191.4 | CM | — |
| 0 | MGO | CONNECTION AT THE MH 3 O'CLOCK |
| 0 | MWL | — |
| 113.8 | TF | — |
| 252.7 | DAGS | — |
| 97.5 | CL | — |
| 233.1 | FM | — |
| 357.4 | FM | — |
| 252.7 | RFJ | — |
| 249.7 | RFJ | — |
| 0 | AMH | 02 0009 |
| 312.2 | RFJ | — |
| 94.4 | CL | — |
| 191.4 | CL | — |
| 180.3 | DAGS | — |
| 0 | MWM | — |
| 254.9 | TFA | — |
| 182.3 | TFA | — |
| 364.8 | AMH | 02 0008 |
| 0 | MGO | CONNECTION AT THE MH 9 O'CLOCK |
| 64.9 | CM | — |
| 256 | RFJ | — |