Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 10, 2017, 08:19 AM
  • 18 0258_18 0257 _10072017_012555.mp4

Date
07/10/2017
W/O
640666
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00672
PipeID
P14086
Time
1:19 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4639
Sewer Name
18 BROADWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_640666_TV18003_JUN2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0258
Downstream MH
18 0257
Dir. of Survey
Downstream
Length Surveyed
182.4 ft.
Total Length
182.4 ft.
Structural Index
3
Structural Quick
3823
Structural Rating
30
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
31
Pipe schematic from manhole 18 0258 to 18 0257
MH: 18 0258MH: 18 0257downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02583.5 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES7.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES39.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES53.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"56.3 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES76.7 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES98.7 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES106.2 ft. RFJ - Roots Fine Joint, from 10 to 11 o'clock, within 8 inches of joint: YES108.6 ft. CM - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES113.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES120.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES130.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"135.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES143.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES182.3 ft. MGO - General Observation - CONNECTION AT MH 9 ACTIVE182.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0257182.4 ft. MGO - General Observation - CONNECTION AT MH 3 ACTIVE

Observation photos (12)

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    3.5 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    7.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    39.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    56.3 ft. - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    76.7 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    98.7 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 10 to 11 o'clock, within 8 inches of joint: YES

    106.2 ft. - Roots Fine Joint, from 10 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    108.6 ft. - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    113.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    120.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    135.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    143.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
53.5TFC
182.4AMH18 0257
130.1TFC
135.4CM
56.3CM
7.4CM
98.7CL
113.7CL
0MWM
182.3MGOCONNECTION AT MH 9 ACTIVE
39.4CM
3.5CM
106.2RFJ
108.6CM
120.9CM
0MWL
182.4MGOCONNECTION AT MH 3 ACTIVE
76.7CL
143.8CM
0AMH18 0258

Properties (5)

additional_info
SC345385
custom_field_two
3
customer
LACSD
datetime
2017-07-10T01:19:36-07:00
sewer_category