Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 11, 2016, 04:36 AM
  • 02 1393_02 1392_20160510_220417.mp4

Date
05/10/2016
W/O
568667
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02964
Time
9:36 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3370
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_568667_TV02220_MAY2016
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Upstream MH
02 1393
Downstream MH
02 1392
Dir. of Survey
Downstream
Length Surveyed
895.1 ft.
Total Length
895.1 ft.
Structural Index
4
Structural Quick
5b3c
Structural Rating
1409
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
1409
Pipe schematic from manhole 02 1393 to 02 1392
MH: 02 1393MH: 02 1392downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13930 ft. MWL - Water Level, 25 %of cross sectional area2 ft. MGO - General Observation - 50% MAG COAT2.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start11.5 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SPORADICALLY770 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish839 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"890.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish895.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1392

Observation photos (3)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SPORADICALLY

    11.5 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SPORADICALLY

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    839 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (10)

DistanceCodeObservation
11.5SRVSPORADICALLY
895.1AMH02 1392
2MGO50% MAG COAT
0MWM
0AMH02 1393
2.1SAV
770SRV
890.2SAV
0MWL
839TF

Properties (5)

additional_info
SC300368
custom_field_two
2
customer
LACSD
datetime
2016-05-10T21:36:22-07:00
sewer_category