Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 10, 2016, 06:06 AM
  • 02 1399_02 1398_20160510_000317.mp4

Date
05/09/2016
W/O
568667
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02970
Time
11:06 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3369
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_568667_TV02220_MAY2016
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Upstream MH
02 1399
Downstream MH
02 1398
Dir. of Survey
Downstream
Length Surveyed
936.5 ft.
Total Length
936.5 ft.
Structural Index
4
Structural Quick
5333
Structural Rating
24
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
4
Overall Quick
Overall Rating
26
Pipe schematic from manhole 02 1399 to 02 1398
MH: 02 1399MH: 02 1398downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13990 ft. MWL - Water Level, 30 %of cross sectional area2 ft. MGO - General Observation - 60% MAG COAT2.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SPORADICALLY23.2 ft. LR - Alignment Right, 20 %31.4 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO78.2 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start327.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"431 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"727.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"739.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"754.6 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish831.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"928.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"931 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO931.1 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish936.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1398

Observation photos (4)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SPORADICALLY

    2.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SPORADICALLY

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO

    31.4 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    78.2 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

    931 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

Observations (18)

DistanceCodeObservation
2MGO60% MAG COAT
327.2TFC
936.5AMH02 1398
0MWM
831.7TFC
931SRV
431TFC
739.6TF
0AMH02 1399
23.2LR
727.2TFC
754.6SRV
31.4SAV
931.1SAV
0MWL
2.1SRVSPORADICALLY
78.2SAV
928.3TF

Properties (5)

additional_info
SC300367
custom_field_two
2
customer
LACSD
datetime
2016-05-09T23:06:42-07:00
sewer_category
GRAVITY