Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 10, 2016, 04:57 AM
  • 02 1401_02 1400_20160509_220756.mp4

Date
05/09/2016
W/O
568667
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02972
Time
9:57 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3369
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_568667_TV02220_MAY2016
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Upstream MH
02 1401
Downstream MH
02 1400
Dir. of Survey
Downstream
Length Surveyed
155.4 ft.
Total Length
155.4 ft.
Structural Index
4
Structural Quick
5231
Structural Rating
13
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
13
Pipe schematic from manhole 02 1401 to 02 1400
MH: 02 1401MH: 02 1400downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 14010 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area2.1 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO2.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start6.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start148.9 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish148.9 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish155.4 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK155.4 ft. AMH - Downstream Manhole, Survey Ends - 02 1400155.4 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK

Observation photos (3)

  • Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO

    2.1 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    6.3 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

Observations (11)

DistanceCodeObservation
2.1SRC
148.9SRV
148.9SAV
155.4MGOCONNECTION AT MH 3 OCLOCK
6.3SAV
2.1SRV
155.4AMH02 1400
0AMH02 1401
0MWM
155.4MGOCONNECTION AT MH 9 OCLOCK
0MWL

Properties (5)

additional_info
SC300367
custom_field_two
2
customer
LACSD
datetime
2016-05-09T21:57:43-07:00
sewer_category
GRAVITY