Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 1, 2017, 09:26 AM
  • 02 1404_02 1403 _01062017_025328.mpg

Date
06/01/2017
W/O
635640
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02975
Time
2:26 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4612
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
WO_635640_TV02220_MAY2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
02 1404
Downstream MH
02 1403
Dir. of Survey
Downstream
Length Surveyed
842.5 ft.
Total Length
842.5 ft.
Structural Index
5
Structural Quick
5a32
Structural Rating
861
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
861
Pipe schematic from manhole 02 1404 to 02 1403
MH: 02 1404MH: 02 1403downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 14042.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.9 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12 ft. MGO - General Observation - BROKEN REBAR89 ft. MGO - General Observation - BROKEN REBAR198 ft. MGO - General Observation - BROKEN REBAR758.1 ft. HSV - Hole Soil Visible, from 07 to 09 o'clock, within 8 inches of joint: YES763.6 ft. HSV - Hole Soil Visible, from 07 to 09 o'clock, within 8 inches of joint: NO813 ft. HSV - Hole Soil Visible, from 03 to 04 o'clock, within 8 inches of joint: NO813 ft. HSV - Hole Soil Visible, from 07 to 09 o'clock, within 8 inches of joint: NO842.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish842.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1403842.5 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (6)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.9 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Hole Soil Visible, from 07 to 09 o'clock, within 8 inches of joint: YES

    758.1 ft. - Hole Soil Visible, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Hole Soil Visible, from 07 to 09 o'clock, within 8 inches of joint: NO

    763.6 ft. - Hole Soil Visible, from 07 to 09 o'clock, within 8 inches of joint: NO

  • Hole Soil Visible, from 03 to 04 o'clock, within 8 inches of joint: NO

    813 ft. - Hole Soil Visible, from 03 to 04 o'clock, within 8 inches of joint: NO

  • Hole Soil Visible, from 07 to 09 o'clock, within 8 inches of joint: NO

    813 ft. - Hole Soil Visible, from 07 to 09 o'clock, within 8 inches of joint: NO

Observations (15)

DistanceCodeObservation
0MWM
7.9SRV
0MWL
12MGOBROKEN REBAR
89MGOBROKEN REBAR
842.5SAP
758.1HSV
2.6SAP
763.6HSV
842.5AMH02 1403
842.5SRV
0AMH02 1404
813HSV
813HSV
198MGOBROKEN REBAR

Properties (4)

additional_info
SC345324
custom_field_two
1
customer
LACSD
datetime