Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 9, 2017, 09:25 AM
Date
06/09/2017
W/O
640674
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00751
PipeID
P19248
Time
2:25 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4574
Sewer Name
20 20TH STREET EAST RELIEF TRUNK
City
PALMDALE
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 20
Page No.
12
Purpose
Routine Assessment
Project
WO_640674_TV20031_JUN2017
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
20 0281
Downstream MH
20 0282
Dir. of Survey
Upstream
Length Surveyed
400.5 ft.
Total Length
400.5 ft.
Structural Index
3
Structural Quick
3O00
Structural Rating
237
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
240
Pipe schematic from manhole 20 0281 to 20 0282
MH: 20 0281MH: 20 0282upstream0 ft. AMH - Upstream Manhole, Survey Ends - 20 02820 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 12 O'CLOCK1.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE1.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish63.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"91.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"115.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"135.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"163.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"172.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"188.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"213.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"241.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"265.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"290 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"314.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"316.1 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - DEBRIS342.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"367.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"398.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start400.5 ft. MWL - Water Level, 25 %of cross sectional area400.5 ft. AMH - Downstream Manhole, Survey Begins - 20 0281400.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observations (23)

DistanceCodeObservation
32.9TFC
265TFC
57.6TFC
187.4TFC
0MWL
159.3TFC
134.9TFC
0AMH20 0281
84.4DSZDEBRIS
110.5TFC
211.8TFC
398.8MGOCOCKROACHES IN MANHOLE
337.3TFC
400.5AMH20 0282
85.7TFC
236.7TFC
398.8SAV
0MGOCOCKROACHES IN MANHOLE
400.5MGOACTIVE CONNECTION AT MH 12 O'CLOCK
284.7TFC
309.2TFC
2SAV
228TBA

Properties (5)

additional_info
SC345250
custom_field_two
3
customer
LACSD
datetime
2017-06-09T02:25:45-07:00
sewer_category
Gravity