Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 17, 2016, 05:26 AM
  • 02 1585_02 2258_20160816_230245.mp4

Date
08/16/2016
W/O
585987
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00231
PipeID
P04038
Time
10:26 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3566
Sewer Name
02 ARIZONA AVENUE TRUNK, SECTION 2
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
WO_585987_TV02010_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1585
Downstream MH
02 2258
Dir. of Survey
Downstream
Length Surveyed
274 ft.
Total Length
274.1 ft.
Structural Index
3
Structural Quick
3323
Structural Rating
15
O&M Index
3
O&M Quick
4221
O&M Rating
11
Overall Index
3
Overall Quick
Overall Rating
26
Pipe schematic from manhole 02 1585 to 02 2258
MH: 02 1585MH: 02 2258downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 15850 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area3.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start17.2 ft. RFJ - Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YES21.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"26.7 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES64.1 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 6"71.5 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES74.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES81.3 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"112.7 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"128.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES147.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES149 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"173.3 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"180.5 ft. MCU - Camera Underwater, Start245.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"249.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES249.8 ft. MCU - Camera Underwater, Finish272.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"274 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish274.1 ft. AMH - Downstream Manhole, Survey Ends - 02 2258

Observation photos (8)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES

    26.7 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    71.5 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    74.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    128.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    147.1 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Camera Underwater, Start

    180.5 ft. - Camera Underwater, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    249.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
26.7SSS
0AMH02 1585
274DAGS
71.5CM
272.1TFC
149TFC
249.8CL
64.1TF
3.1DAGS
74.5CM
112.7TF
245.2TF
81.3TF
249.8MCU
147.1CM
21.4TF
0MWM
274.1AMH02 2258
128.9CL
17.2RFJ
180.5MCU
173.3TF
0MWL

Properties (5)

additional_info
SC305899
custom_field_two
3
customer
LACSD
datetime
2016-08-16T22:26:19-07:00
sewer_category
Gravity