Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 27, 2016, 10:27 AM
  • 14 0456_14 0455_27052016_032819.mp4

Date
05/27/2016
W/O
574295
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00570
PipeID
P18544
Time
3:27 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3514
Sewer Name
14 AVENUE "I" TRUNK
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
04
Purpose
V
Project
WO_574295_TV14045_JUNE2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
14 0455
Downstream MH
14 0456
Dir. of Survey
Upstream
Length Surveyed
364.5 ft.
Total Length
364.5 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2N00
O&M Rating
148
Overall Index
2
Overall Quick
Overall Rating
151
Pipe schematic from manhole 14 0455 to 14 0456
MH: 14 0455MH: 14 0456upstream0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0 ft. MSA - Survey Abandoned - DUE TO SETTLED DEPOSITS. REVERSAL COMPLETE.2.6 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES17.6 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"20.6 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"68.4 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"71.9 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"119.7 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"123.3 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"132.1 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES171.6 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"175.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"220.3 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"223.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"237.9 ft. CM - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES271.6 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"274.5 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"323.3 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"325.7 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"362.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start364.5 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK364.5 ft. MWM - Water Mark, 35 %of cross sectional area364.5 ft. AMH - Downstream Manhole, Survey Begins - 14 0455364.5 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

    126.6 ft. - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Deposits Settled Compacted,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES

    232.4 ft. - Deposits Settled Compacted, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
364.5DAGS
232.4DSC
361.9DSZ
90TFA
144.2TFC
343.9TFC
244.8TFC
141.3TFC
292.6TFC
41.2TFC
192.9TFC
364.5MSADUE TO SETTLED DEPOSITS. REVERSAL COMPLETE.
92.9TFC
0MGOCONNECTION AT MH 3 O'CLOCK
346.9TFC
0MWM
126.6CM
0AMH14 0455
38.8TFC
241.2TFA
0MWL
2DAGS
189.3TFC
296.1TFC

Properties (5)

additional_info
SC305644
custom_field_two
4
customer
LACSD
datetime
2016-05-27T03:27:41-07:00
sewer_category