- Date
- 05/26/2016
- W/O
- 574295
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00570
- PipeID
- P18547
- Time
- 2:15 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K3512
- Sewer Name
- 14 AVENUE "I" TRUNK
- City
- LANCASTER
- Loc. details
- Main Highway - Suburban/Rural
- Location Code
- B
- Use of Sewer
- Sanitary Sewer
- District
- District 14
- Page No.
- 04
- Purpose
- Routine Assessment
- Project
- WO_574295_TV14045_JUNE2016
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 12 in.
- Upstream MH
- 14 0458
- Downstream MH
- 14 0459
- Dir. of Survey
- Upstream
- Length Surveyed
- 45.3 ft.
- Total Length
- 45.3 ft.
- Structural Index
- 0
- Structural Quick
- 0000
- Structural Rating
- 0
- O&M Index
- 2
- O&M Quick
- 4131
- O&M Rating
- 39
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 39
Pipe schematic from manhole 14 0458 to 14 0459 Observation photos (6)

0 ft. - General Observation - COCKROACHES IN MANHOLE

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

12.4 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Start

41.9 ft. - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 6"

45.3 ft. - Survey Abandoned - DUE TO GREASE/OBSTACLE

45.3 ft. - Obstacles Other, 15 %of cross sectional area, from 05 to 07 o'clock - GREASE