Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 25, 2016, 11:51 AM
  • 14 0419A_14 0419_25052016_045200.mp4

Date
05/25/2016
W/O
573476
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00578
PipeID
P18503
Time
4:51 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3510
Sewer Name
14 TRUNK "B"
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
04
Purpose
Routine Assessment
Project
WO_573476_JUNE2016
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
14 0419
Downstream MH
14 0419A
Dir. of Survey
Upstream
Length Surveyed
330.7 ft.
Total Length
330.7 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
195
O&M Index
2
O&M Quick
412L
O&M Rating
134
Overall Index
3
Overall Quick
Overall Rating
329
Pipe schematic from manhole 14 0419 to 14 0419A
MH: 14 0419MH: 14 0419Aupstream0 ft. AMH - Upstream Manhole, Survey Ends - 14 0419A1.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish1.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish20.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"44.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"66.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"94 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"107.2 ft. MGO - General Observation - RUN LIST STATES MH AT 223'.118.1 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"146.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"171.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"196.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"220.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"249.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"273.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"298.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"321.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"328.7 ft. MGO - General Observation - MAG COATING 80%328.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start328.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start330.7 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK330.7 ft. MWL - Water Level, 35 %of cross sectional area330.7 ft. AMH - Downstream Manhole, Survey Begins - 14 0419330.7 ft. MWM - Water Mark, 60 %of cross sectional area

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (24)

DistanceCodeObservation
9.4TFC
2MGOMAG COATING 80%
263.8TFC
212.6TFC
57.2TFC
32.3TFC
329.3SAP
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
236.7TFC
330.7AMH14 0419A
0MWL
81.6TFC
2DAGS
0AMH14 0419
223.5MGORUN LIST STATES MH AT 223'.
2SAP
134.6TFC
310.6TFC
159.2TFC
184.6TFC
110.2TFC
285.9TFC
0MWM
329.3DAGS

Properties (5)

additional_info
SC305640
custom_field_two
3
customer
LACSD
datetime
2016-05-25T04:51:36-07:00
sewer_category