Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 25, 2016, 10:58 AM
  • 14 0434_14 0433A_25052016_035822.mp4

Date
05/25/2016
W/O
573476
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00578
PipeID
P25703
Time
3:58 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3510
Sewer Name
14 TRUNK "B"
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
05
Purpose
Routine Assessment
Project
WO_573476_JUNE2016
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
14 0434
Downstream MH
14 0433A
Dir. of Survey
Downstream
Length Surveyed
288.6 ft.
Total Length
288.6 ft.
Structural Index
2
Structural Quick
3J2N
Structural Rating
323
O&M Index
2
O&M Quick
413C
O&M Rating
175
Overall Index
2
Overall Quick
Overall Rating
498
Pipe schematic from manhole 14 0434 to 14 0433A
MH: 14 0434MH: 14 0433Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 04340 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start41.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"65.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"90.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"118.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"143.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"168 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"192.2 ft. MWLS - Water Level, Sag in pipe, 30 %of cross sectional area, Start192.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"192.3 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start245 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"269.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"287.5 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish287.5 ft. MWLS - Water Level, Sag in pipe, 30 %of cross sectional area, Finish287.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish287.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish287.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish288.6 ft. AMH - Downstream Manhole, Survey Ends - 14 0433A288.6 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Water Level, Sag in pipe, 30 %of cross sectional area, Start

    192.2 ft. - Water Level, Sag in pipe, 30 %of cross sectional area, Start

Observations (24)

DistanceCodeObservation
287.5DSZ
269.4TFC
192.3DSZ
41.5TFC
287.5MWLS
0AMH14 0434
192.2MWLS
287.5DAGS
245TFC
2SSS
288.6AMH14 0433A
0MWL
168TFC
287.5SAV
2DAGS
288.6MGOACTIVE CONNECTION AT MH 9 O'CLOCK
143.7TFC
2SAV
118.8TFC
65.7TFC
192.2TFC
287.5SSS
90.5TFC
0MWM

Properties (5)

additional_info
SC305640
custom_field_two
2
customer
LACSD
datetime
2016-05-25T03:58:01-07:00
sewer_category