Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 20, 2016, 08:10 AM
  • 05 1645_05 1644 _062016_011051.mpg

Date
06/20/2016
W/O
563399
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00539
PipeID
P06868
Time
1:10 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3399
Sewer Name
05 WEST TORRANCE TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
30
Purpose
Routine Assessment
Project
WO_563399_TV05132_JUNE2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1645
Downstream MH
05 1644
Dir. of Survey
Downstream
Length Surveyed
310.6 ft.
Total Length
310.6 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
180
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
180
Pipe schematic from manhole 05 1645 to 05 1644
MH: 05 1645MH: 05 1644downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH CAPPED 9 O'CLOCK0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH CAPPED 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 16454.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start11.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"43.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"83 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"118.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"123.7 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"158.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"198.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"242.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"281.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"304.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish310.6 ft. AMH - Downstream Manhole, Survey Ends - 05 1644310.6 ft. MGO - General Observation - CONNECTION AT THE MH CAPPED 9 O'CLOCK310.6 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK

Observation photos (2)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    123.7 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

Observations (19)

DistanceCodeObservation
310.6AMH05 1644
83TF
281.9TFC
0MWL
0MGOCONNECTION AT THE MH CAPPED 9 O'CLOCK
4.6CM
242.5TF
304.3CM
0MWM
158.3TF
198.4TF
310.6MGOCONNECTION AT THE MH CAPPED 9 O'CLOCK
118.6TFC
11.7TF
0MGOCONNECTION AT THE MH CAPPED 3 O'CLOCK
0AMH05 1645
43.7TF
310.6MGOCONNECTION AT THE MH 3 O'CLOCK
123.7TB

Properties (5)

additional_info
SC300399
custom_field_two
3
customer
LACSD
datetime
2016-06-20T01:10:20-07:00
sewer_category
Gravity