Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 20, 2016, 07:56 AM
  • 05 1646_05 1645 _062016_005634.mpg

Date
06/20/2016
W/O
563399
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00539
PipeID
P06869
Time
12:56 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3399
Sewer Name
05 WEST TORRANCE TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
30
Purpose
Routine Assessment
Project
WO_563399_TV05132_JUNE2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1646
Downstream MH
05 1645
Dir. of Survey
Downstream
Length Surveyed
260.5 ft.
Total Length
260.5 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
150
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
150
Pipe schematic from manhole 05 1646 to 05 1645
MH: 05 1646MH: 05 1645downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH capped 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 16465.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start63.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"102.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"142.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"182 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"225.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"248.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"254.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish260.5 ft. AMH - Downstream Manhole, Survey Ends - 05 1645260.5 ft. MGO - General Observation - CONNECTION AT THE MH CAPPED 9 O'CLOCK260.5 ft. MGO - General Observation - CONNECTION AT THE MH 3 CAPPED O'CLOCK

Observation photos (1)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
63.5TF
0MWL
102.9TF
0MGOCONNECTION AT THE MH 9 O'CLOCK
182TF
5.8CM
142.2TFC
0MWM
260.5AMH05 1645
0MGOCONNECTION AT THE MH capped 3 O'CLOCK
225.3TF
254.8CM
0AMH05 1646
260.5MGOCONNECTION AT THE MH CAPPED 9 O'CLOCK
260.5MGOCONNECTION AT THE MH 3 CAPPED O'CLOCK
248.3TFC

Properties (5)

additional_info
SC300399
custom_field_two
3
customer
LACSD
datetime
2016-06-20T00:56:04-07:00
sewer_category
Gravity