Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 15, 2016, 07:58 AM
  • 05 1665_05 1664 _061516_005849.mpg

Date
06/15/2016
W/O
563399
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00539
PipeID
P06889
Time
12:58 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3397
Sewer Name
05 WEST TORRANCE TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
33
Purpose
Routine Assessment
Project
WO_563399_TV05132_JUNE2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1665
Downstream MH
05 1664
Dir. of Survey
Downstream
Length Surveyed
273.5 ft.
Total Length
273.5 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
156
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
156
Pipe schematic from manhole 05 1665 to 05 1664
MH: 05 1665MH: 05 1664downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 16650 ft. MGO - General Observation - PIPE IS 18"0 ft. MWM - Water Mark, 20 %of cross sectional area7.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start41.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6", 6"92.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"143.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"193.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"228.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"268 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish273.5 ft. AMH - Downstream Manhole, Survey Ends - 05 1664273.5 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK273.5 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0MWL
143.1TFC
228.7TFC
0AMH05 1665
7.8CM
0MGOPIPE IS 18"
41.7TF
273.5AMH05 1664
193.7TF
92.5TF
0MWM
268CM
273.5MGOCONNECTION AT THE MH 3 O'CLOCK
273.5MGOCONNECTION AT THE MH 9 O'CLOCK

Properties (5)

additional_info
SC300397
custom_field_two
3
customer
LACSD
datetime
2016-06-15T00:58:23-07:00
sewer_category
Gravity