Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 20, 2016, 05:34 AM
  • 02 0800_02 0799_20160719_235634.mp4

Date
07/19/2016
W/O
574316
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00294
PipeID
P03366
Time
10:34 PM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3658
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
WO_574316_TV02111_JUNE2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0800
Downstream MH
02 0799
Dir. of Survey
Downstream
Length Surveyed
345.6 ft.
Total Length
345.6 ft.
Structural Index
3
Structural Quick
3700
Structural Rating
21
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
26
Pipe schematic from manhole 02 0800 to 02 0799
MH: 02 0800MH: 02 0799downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 08000 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE0 ft. MWM - Water Mark, 15 %of cross sectional area26.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES27.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"28.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start31.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"77.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"80.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"112.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish127.2 ft. CM - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES132.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"135.8 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"139.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start181.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"184.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"237.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"255.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"261.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish272.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES292.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"295.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"303.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES333.2 ft. CM - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES335.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"345.6 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE345.6 ft. AMH - Downstream Manhole, Survey Ends - 02 0799

Observation photos (9)

  • General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE

    0 ft. - General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    28.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    31.2 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    77.2 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    135.8 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    184.7 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    272.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

    333.2 ft. - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

  • General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE

    345.6 ft. - General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE

Observations (28)

DistanceCodeObservation
0MWL
184.7TFC
0AMH02 0800
139.8CM
31.2TFC
303.9CM
295.7TFC
132.5TFA
27.7TFA
345.6MGOCONNECTION AT THE MH 9 O'CLOCK ACTIVE
28.7CM
0MGOCONNECTION AT THE MH 3 O'CLOCK ACTIVE
135.8TBC
181.4TFC
237.3TFC
292.4TFC
80.7TFC
0MWM
127.2CM
255.7TFA
272.5CM
77.2TF
112.5CM
335.6TFA
333.2CM
26.2CM
345.6AMH02 0799
261.3CM

Properties (4)

additional_info
SC305537
custom_field_two
3
customer
LACSD
datetime
2016-07-19T22:34:26-07:00