Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 13, 2016, 10:07 AM
  • 02 0805_02 0804_20160713_033344.mp4

Date
07/13/2016
W/O
574316
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00294
PipeID
P03371
Time
3:07 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3565
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
WO_574316_TV02111_JUNE2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0805
Downstream MH
02 0804
Dir. of Survey
Downstream
Length Surveyed
354.2 ft.
Total Length
354.2 ft.
Structural Index
3
Structural Quick
3G22
Structural Rating
119
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
122
Pipe schematic from manhole 02 0805 to 02 0804
MH: 02 0805MH: 02 0804downstream0 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 08050 ft. MWM - Water Mark, 20 %of cross sectional area3.2 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES47.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"50.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"86.2 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES89.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"95 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.9 ft. CC - Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES145.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"148.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"148.9 ft. CS - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES159.8 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES166.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"174.9 ft. CM - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES, Start190.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"232.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"240.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"291.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"294.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"333.7 ft. RMC - Roots Medium Connection, from 08 to 10 o'clock, 15 %, within 8 inches of joint: NO336 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"338.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"352.6 ft. CM - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES, Finish354.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0804

Observation photos (8)

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    3.2 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    50.3 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    86.2 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

    128.9 ft. - Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

    148.9 ft. - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    159.8 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES, Start

    174.9 ft. - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Connection, from 08 to 10 o'clock, 15 %, within 8 inches of joint: NO

    333.7 ft. - Roots Medium Connection, from 08 to 10 o'clock, 15 %, within 8 inches of joint: NO

Observations (27)

DistanceCodeObservation
0MGOLATERAL AT MH 3 OCLOCK
338.8TFC
148.9CS
86.2CM
240.9TFC
50.3TFC
0MWL
159.8CM
128.9CC
336TF
291.2TFC
333.7RMC
148.3TFC
89.1TFC
0AMH02 0805
166.9TF
354.2AMH02 0804
0MWM
3.2CL
47.2TF
294.3TFC
174.9CM
232.1TF
190.1TFC
352.6CM
95TF
145.5TFC

Properties (4)

additional_info
SC305873
custom_field_two
3
customer
LACSD
datetime
2016-07-13T03:07:15-07:00