- Date
- 08/11/2016
- W/O
- 252431
- Weather
- Dry
- Operator/Surveyor
- J. HARTOOG
- Sewer ID
- Z00250
- PipeID
- P02717
- Time
- 10:21 PM
- Certificate
- U-507-03-3386
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K3681
- Sewer Name
- 02 DOWNEY AVENUE EXTENSION TRUNK
- City
- PARAMOUNT, CA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 32
- Purpose
- Routine Assessment
- Project
- WO_252431_TV02049_AUG2016
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 18 in.
- Width
- 18 in.
- Upstream MH
- 02 0396
- Downstream MH
- 02 0395
- Dir. of Survey
- Downstream
- Length Surveyed
- 225.6 ft.
- Total Length
- 225.6 ft.
- Structural Index
- 3
- Structural Quick
- 3100
- Structural Rating
- 3
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 3
Pipe schematic from manhole 02 0396 to 02 0395 Observation photos (4)

0 ft. - Water Level, 15 %of cross sectional area

5.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

210.1 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"

215.6 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"