Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 8, 2016, 10:35 AM
  • 02 0386_02 0385 _20160808_044913.mp4

Date
08/08/2016
W/O
252431
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00250
PipeID
P02704
Time
3:35 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3677
Sewer Name
02 DOWNEY AVENUE EXTENSION TRUNK
City
BELLFLOWER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
WO_252431_TV02049_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0385
Downstream MH
02 0386
Dir. of Survey
Upstream
Length Surveyed
288.9 ft.
Total Length
288.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
4121
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 02 0385 to 02 0386
MH: 02 0385MH: 02 0386upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 03862.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish7.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"14.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"42 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"62.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"86.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"117.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"136 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"168.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"186.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"202.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"241.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"254.6 ft. RFJ - Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YES278.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"281.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start288.9 ft. MWL - Water Level, 10 %of cross sectional area288.9 ft. AMH - Downstream Manhole, Survey Begins - 02 0385288.9 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE288.9 ft. MWM - Water Mark, 15 %of cross sectional area

Observation photos (3)

  • General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE

    0 ft. - General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    7.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    226.2 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"

Observations (20)

DistanceCodeObservation
226.2TBA
246.9TFC
7.2DAGS
288.9AMH02 0386
0MWL
286.7DAGS
10.2TFA
152.9TFC
281.6TF
0AMH02 0385
274.7TF
47.3TFC
102.1TFA
0MGOCONNECTION AT THE MH 9 O'CLOCK ACTIVE
34.3RFJ
120.8TF
0MWM
171.6TFC
202.8TF
86.2TF

Properties (4)

additional_info
SC306007
custom_field_two
4
customer
LACSD
datetime