Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 7, 2016, 10:38 AM
  • 01 1001_01 1000_07092016_033857.mp4

Date
09/07/2016
W/O
585982
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00221
PipeID
P01842
Time
3:38 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3580
Sewer Name
01 VERNON EXTENSION TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
WO_585982_TV01065_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
01 1001
Downstream MH
01 1000
Dir. of Survey
Downstream
Length Surveyed
284.5 ft.
Total Length
284.6 ft.
Structural Index
3
Structural Quick
3400
Structural Rating
12
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole 01 1001 to 01 1000
MH: 01 1001MH: 01 1000downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 100014.4 ft. CM - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES22.8 ft. CM - Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES110.5 ft. CM - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES155.6 ft. CM - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES284.6 ft. AMH - Downstream Manhole, Survey Ends - 01 1000

Observation photos (4)

  • Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

    14.4 ft. - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    22.8 ft. - Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    110.5 ft. - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    155.6 ft. - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
110.5CM
22.8CM
155.6CM
14.4CM
0MWL
284.6AMH01 1000
0MWM
0AMH01 1000

Properties (5)

additional_info
SC306170
custom_field_two
4
customer
LACSD
datetime
2016-09-07T03:38:22-07:00
sewer_category