Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 20, 2016, 10:56 AM
  • 05 1640_05 1639 _062016_035645.mp4

Date
06/20/2016
W/O
563400
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00539
PipeID
P06863
Time
3:56 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3400
Sewer Name
05 WEST TORRANCE TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
WO_563400_TV05275_JUNE2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1640
Downstream MH
05 1639
Dir. of Survey
Downstream
Length Surveyed
227.9 ft.
Total Length
227.9 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
126
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
126
Pipe schematic from manhole 05 1640 to 05 1639
MH: 05 1640MH: 05 1639downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 16400 ft. MWM - Water Mark, 30 %of cross sectional area16 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start23.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"72.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"122.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"174.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"224.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"224.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish227.9 ft. AMH - Downstream Manhole, Survey Ends - 05 1639227.9 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    16 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWL
72.4TF
122.8TFA
23.4TFC
224.6CM
224.1TFC
0AMH05 1640
174.5TFC
227.9AMH05 1639
0MWM
227.9MGOCONNECTION AT THE MH 3 O'CLOCK
16CM

Properties (5)

additional_info
SC300400
custom_field_two
3
customer
LACSD
datetime
2016-06-20T03:56:24-07:00
sewer_category