Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 20, 2016, 10:25 AM
  • 05 1644_05 1643 _062016_032554.mp4

Date
06/20/2016
W/O
563400
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00539
PipeID
P06867
Time
3:25 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3400
Sewer Name
05 WEST TORRANCE TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
WO_563400_TV05275_JUNE2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1643
Downstream MH
05 1644
Dir. of Survey
Upstream
Length Surveyed
310.5 ft.
Total Length
310.5 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
174
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
174
Pipe schematic from manhole 05 1643 to 05 1644
MH: 05 1643MH: 05 1644upstream0 ft. MGO - General Observation - CONNECTION AT THE MH CAPPED 3 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 05 16446.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish17.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"67.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"120.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"170.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"232.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"270.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"297.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start310.5 ft. AMH - Downstream Manhole, Survey Begins - 05 1643310.5 ft. MGO - General Observation - CONNECTION AT THE MH CAPPED 9 O'CLOCK310.5 ft. MWL - Water Level, 10 %of cross sectional area310.5 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (1)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    13.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
0AMH05 1643
310.5MGOCONNECTION AT THE MH CAPPED 3 O'CLOCK
13.3CM
190.2TFC
0MGOCONNECTION AT THE MH CAPPED 9 O'CLOCK
310.5MGOCONNECTION AT THE MH 9 O'CLOCK
304.3CM
293.3TF
242.8TF
310.5AMH05 1644
0MWL
39.6TFC
139.8TFC
78.2TF
0MWM

Properties (5)

additional_info
SC300400
custom_field_two
3
customer
LACSD
datetime
2016-06-20T03:25:16-07:00
sewer_category
Gravity