Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 20, 2016, 10:39 AM
  • 05 1641_05 1640 _062016_035228.mp4

Date
06/20/2016
W/O
563400
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00539
PipeID
P06864
Time
3:39 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3400
Sewer Name
05 WEST TORRANCE TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
WO_563400_TV05275_JUNE2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1641
Downstream MH
05 1640
Dir. of Survey
Downstream
Length Surveyed
55.4 ft.
Total Length
55.4 ft.
Structural Index
3
Structural Quick
3A00
Structural Rating
30
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
30
Pipe schematic from manhole 05 1641 to 05 1640
MH: 05 1641MH: 05 1640downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 16410 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK3.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start28.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"55.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish55.4 ft. AMH - Downstream Manhole, Survey Ends - 05 1640

Observation photos (1)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWM
55.4CM
3.9CM
55.4AMH05 1640
0MWL
0AMH05 1641
0MGOCONNECTION AT THE MH 3 O'CLOCK
28.8TF

Properties (5)

additional_info
SC300400
custom_field_two
3
customer
LACSD
datetime
2016-06-20T03:39:53-07:00
sewer_category